header("Pragma: no-cache"); header("Cache-Control: no-cache,must-revalidate"); ?>
Overview
FILK has been at the forefront of fundamental and applied research on all aspects of fire safety. FILK research is targeted primarily at promoting performance of fire protection and safety materials and products. With the most extensive laboratories in Korea, a highly qualified team of expert engineers, we are able to deliver practical solutions, technical advice and a bespoke service to a wide range of clients. The research ranges from shorter term, problem-solving studies to the longer term strategic.
FILK Quality Certification
Benefits
FILK Quality Certification gives you a number of tangible and intangible benefits, such as premium discount, market entry, differentiation, confidence etc. It also benefits everyone in the supply chain, from the manufacturer to the end client, and eventually contributes to the improvement of national safety to fire.
Process of FILK Quality Certification
List of Companies manufacturing certified products by FILK
AUTOMATIC FIRE DETECTION SYSTEM
SAFE SYSTEM CO., LTD | www.safesystem.co.kr |
---|---|
WOOSEOK SYSTEM CO., LTD | - |
SIEMENS LTD | www.siemens.co.kr/bt |
PRO-TECH FIRE PREVENTION CO., LTD | www.protech7.com |
JOHNSONCONTROLS INTERNATIONAL KOREA CO., LTD | www.dbefire.com |
ALLLITELIFE CO., LTD | www.alllitelife.com |
FIRE RESISTANCE PENETRATION SEALING SYSTEMS
WACKER CHEMICAL KOREA | www.wacker.com |
---|---|
HRS CO., LTD | www.hrssilicone.com |
KCC SILICONE CORPORATION JUNJU PLANT | www.kccsilicone.com |
AUTOMATIC EXTINGUISHER
PNCTECH CO., LTD | www.pnctech.co.kr |
---|---|
NOBLE PROTECTION COMPANY INC | www.noble119.com |
FIRE ESCAPE MASK
HANCOM LIFECARE INC | www.hancomlifecare.com |
---|
INCOMBUSTIBLE INTERIOR FINISHING MATERIALS
KCC CORPORATION - EUNYANG PLANT | www.kccworld.co.kr |
---|
FIRE EXTINGUISHER
SAMWOO INSTRUMENT, INC | www.sw119.com |
---|
CLEAN AGENT FIRE SUPPRESSION SYSTEM
S-TEC SYSTEM | www.s-tec.co.kr |
---|
MONITORING AND CONTROL SYSTEM FOR WATER-BASED FIRE PROTECTION SYSTEMS
VISION ENGINEERING CO., LTD | www.vision1.co.kr |
---|
AUTOMATIC EXTINGUISHING DEVICE
GASTRON CO., LTD | www.gastron.com |
---|
Where a material is required not to be capable of producing excessive quantities of smoke and toxic products or not to give rise to toxic hazards at elevated temperatures, the material shall comply with this test. The maximum specific optical density of smoke (Ds max) shall be obtained for each test. When making toxicity measurements, the sampling of fumes shall be made during the testing of the second and the third specimen at each test condition, from the geometrical centre of the chamber at the time when the maximum specific optical density of smoke is reached. The concentration of each toxic gas shall be determined as parts per million (ppm) in the chamber volume.
Performance criteria
Surface of bulkheads, linings or ceilings | Primary deck coverings | Floor coverings | Plastic pipes | ||
---|---|---|---|---|---|
Dm* | ≤ 200 | ≤ 400 | ≤ 500 | ≤ 400 | |
Toxicity | CO | ≤ 1,450 ppm | |||
HBr | ≤ 600 ppm | ||||
HCl | ≤ 600 ppm | ||||
HCN | ≤ 140 ppm | ||||
HF | ≤ 600 ppm | ||||
SO2 | ≤ 120 ppm (200 ppm for floor coverings) | ||||
NOx | ≤ 350 ppm |
*Dm is An average (Dm) of the maximum specific optical density of smoke (Ds max) of three tests at each test condition
Specimen preparation and test fee
Test method | Dimensions(mm) | Number required | Test fee | Remark |
---|---|---|---|---|
IMO. FTP Code Part 2(Smoke & Toxicity Test) | ength : 75(-1), width : 75(-1), thickness : ??25 |
12 | 2,613,000 KRW (3,135,600 KRW) | For performance verification test (For Ship register type approval test) |
[ Smoke Density Chamber ]
[ Gas analyzer(FT-IR) ]
Application procedures
Where a product is required to have a surface with low flame-spread characteristics, the product shall comply with this test. Where the primary deck coverings are required to be not readily ignitable, they shall comply with this test. The test method involves mounting the conditioned specimen in a well-defined flux field and measuring the time of ignition, spread of flame and its final extinguishment, together with a stack thermocouple signal as an indication of heat release by the specimen during burning. The following data shall be derived from the test results : CFE, Qsb, Qt and Qp.
Performance criteria
Bulkhead, wall and ceiling linings | Floor coverings | Primary deck coverings | |
---|---|---|---|
CFE (kW/m2) | ≥ 20.0 | ≥ 7.0 | ≥ 7.0 |
Qsb (MJ/m2) | ≥ 1.5 | ≥ 0.25 | ≥ 0.25 |
Qt (MJ) | ≤ 0.7 | ≤ 2.0 | ≤ 2.0 |
Qp (kW) | ≤ 4.0 | ≤ 10.0 | ≤ 10.0 |
Burning droplets | Not produced | No more than 10 burning drops | Not produced |
*Where:
Specimen preparation and test fee
Test method | Dimensions(mm) | Number required | Test fee | Remark |
---|---|---|---|---|
1. IMO. Res. A. 653(16)> 2. IMO. Res. A. 687(17) | length : 800(-5) width : 155(-5) thickness* | 6 | 1,605,500 KRW (1,926,600 KRW) | For performance verification test (For Ship register type approval test) |
* Materials and composites of normal thickness 50 mm or less shall be tested using their full thickness. For materials and composites of normal thickness greater than 50 mm, the required specimens shall be obtained by cutting away the unexposed face to reduce the thickness between 47 mm and 50 mm.
[ Smoke Density Chamber ]